Technical Specification
The FSC-M240 is a digital controller with a high-resolution touch screen. It controls and monitors up to 240 motorized fire protection or smoke extraction dampers and 120 smoke detectors, as well as 120 thermoelectric triggers via Modbus or BACnet, with optional cloud access.
Electrical Data:
* Rated voltage: 5 V DC (230V connection cable included)
* Power consumption: < 10 W, 3A max.
* Connections: Plug connections and clamp connections
Communication / Modbus:
* Protocol: Modbus RTU
* Medium: RS-485, not electrically isolated
* Transmission formats: Specified by Modbus RTU standards
* Baud rates: 9,600 bps for Modbus
* Response time: <500 ms
* Termination: 120Ω termination resistor, bridge on PCB per zone available. Position the bridge if the FSC-M240 is the last Modbus device in the string.
* Addresses: Modbus addresses 121 (Zone1) and 122 (Zone2) for the FSC-M240
* Modbus Connection (Port): Connection in the FSC-M240 for integration into any higher-level Modbus system, allowing access and monitoring of parameters in connected UFC24(-2(-230), UFC230-2 devices.
Communication / BACnet:
* Protocol: BACnet MS/TP
* Medium: RS-485, not electrically isolated
* Number of nodes per string: Max. 2 strings of 60 BACnet devices (UFC24(-230), UFC24-2, UFC230-2), without repeater.
* Baud rates: 9,600, 19,200, 38,400, 76,800 (automatic detection)
* Response time: <100 ms
* BACnet Instance Number: Zone1: 804121; Zone2: 804122, FSC-UFC... Addresses 1-60 (Zone1) and 61-120 (Zone2).
Safety:
* Protection class: III (low voltage)
* Protection degree: IP42, housing made of non-flammable polycarbonate
* EMC Emissions: EN61000-6-3 and EN55022
* EMC Immunity: EN50130-4 and EN55024
* Electrical safety: EN60950-1
* Rated impulse voltage: 2.5 kV (EN 60730-1)
* Ambient temperature: 10 … + 30 °C
* Storage temperature: 0 … + 40 °C
* Humidity test: 95% r.H., non-condensing (EN 60730-1)
* Maintenance: Maintenance-free
Mechanical Data:
* Width: 135 mm
* Length: 185 mm
* Height: 75 mm
Installation: Mounted on DIN rail or screwed.