Skip to main content
GT45000S programmable temperature transmitter

GT45000S Georgin Italy Sales

If you are looking for a reliable supplier where you can purchase the GT45000S programmable temperature transmitter, you are in the right place. PARTELLI sells in the Italy marketGeorgin all product groups belonging to the brand, with fast delivery times and competitive prices.

GT45000S programmable temperature transmitter
ProductGT45000S
BrandGeorgin
HS Code85389099
CountryItaly
Request a price
Delivery time: Determined at the time of quotation
VISA Mastercard Bank Transfer

Technical Specification

Temperature universal
transducer
programmable via USB and
DIP switch
for Pt, Ni, KTY and TC
standard sensors, resistance, mV
and potentiometry,
modular housing for DIN rail mounting,
Width 6.2 mm, protection class: IP 20
Input signal Pt 100/Pt 200/Pt 500/
Pt 1000, sensor connection: 2-wire,
3-wire, 4-wire
Ni 100/Ni 200/Ni 500/Ni 1000,
sensor connection: 2-wire, 3-wire,
4-wire
Thermocouples types B, E, J, K, L, N, R,
S, T, U, W5Re_W26Re, W3Re_W25Re
Comparator: internal, external,
uncompensated, manual setting
minimum measurement range: 50 K
output (progr.) 0... 20 mA, 4... 20 mA,
0... 5 V, 1... 5 V, 0... 10 V, 2... 10 V, 0... 10
mA, 2... 10 mA
Output curve rising/falling
Transmission error < 0.1% of E.
Measurement rate 4/s
Auxiliary power 24 V DC, 16.8 V... 31.2 V

DC, approx. 0.8 W
Safe separation EN 61140,
3-port isolation up to 300 V AC/DC all
circles against each other
Test voltage 3 kV, 50 Hz input versus
Output versus auxiliary energy
Working voltage 600 V AC/DC at
surge category II, and
Contamination level 2 between all
circles
ref. GT45000S
Function: Universal input converter - 1
Channel
Input (I): RTD100 2/3/4 wires, RTD1000,
Ni100, Ni1000, TC
Input (V): KTY, Res. 0... 5000 ohms
Pot.100Ohm to 50kOhm
Output (I): Active: 0/4... 20mA, 0/2... 10mA
(=600ohms @20mA)
Output (V): 0/2... 10V, 0/1... 5V
(=2kOhm @10V)
Power supply: 16.8V... 31.2Vdc (0.9W)
Configuration: DIP switches or USB -
GEORGIN software
Isolation: 3KV
Accuracy: < 0.1% full scale